Fireray 3000 End to End Infrared Optical Beam Smoke Detector (3000-101)
Fireray
Fireray 3000 End to End Infrared Optical Beam Smoke Detector
The Fireray 3000 end to end optical beam smoke detector has been designed to protect large open space applications where standard ceiling mounted smoke detectors would not be suitable. The transmitter head emits an infrared beam to a separate receiver using an LCD display controller. If smoke passes through the beam, the alarm signal is activated. The Fireray 3000 has a programmable sensitivity level, meaning that the alarm activation point can be adjusted to suit environments where dust or exhaust fumes may be present.
Features
- Allows for 2 detectors per system controller.
- Range 5 to 120 metres, configurable per set of detectors.
- Integral laser alignment in receiver.
- 2-wire interface between controller and receiver.
- Separate fire and fault relays per detector.
- Low level controller with LCD display.
- Programmable sensitivity and fire/fault delay.
- Automatic Gain Control (AGC) for drift compensation.
- First Fix concept for transmitter, receiver and controller.
- Multiple cable gland knockouts for ease of wiring.
- Transmitter can be powered from controller.
- Patented Light Cancellation Technology (LCT) cancels unwanted light, including sunlight, sodium lamps and fluorescent lighting.
Specifications
- Weight : 0.85kg
- Dimensions (HxWxD) : Controller: 124x203x71.5mm, Transmitter & Receiver: 77x78x161mm
- Operating Range : 5 to 120m
- Operating Voltage : 12 to 36V DC +/- 10%
- Operating Current : Controller (with 1 or 2 receivers): 14mA (constant) Transmitter: 8mA (per transmitter)
- IP Rating : IP54
- Relative Humidity (non-condensing) : 93%
- Operating Temperature (non-condensing) : UL: -20°C to +55°C EN54: -10°C to +55°C
Downloads
- Datasheet (Adobe PDF)