Lexicomm ViLX-ILB Type B Refuge Point With Integral Induction Loop
Vox Ignis
Lexicomm ViLX-ILB Type B Refuge Point With Integral Induction Loop
The ViLX-ILB has been designed to meet the requirements for a Type B outstation with an integral audio frequency induction loop (AFILS). The design has been optimised to produce the horizontal field as required by BS5839-9:2011, overcoming the limitations traditionally associated with a wall mounted induction loop.
To aid location the unit has a high contrast design incorporating a highly visible Braille enhanced call button which flashes green in normal conditions, flashes red when ringing, and is solid red when a call is connected.
The ViLX-ILB is compatible with the full range of Lexicomm master stations and system expander panels and is fully monitored and battery backed up. The outstation is supplied with a brushed stainless and green perspex finish and available in flush or surface mount versions.
Suitability
The ViLX-ILB is a Type B outstation as defined in BS5839-9:2011, and is designed to be used by the public as a disabled refuge call point with AFILS for the hard of hearing.
Type B outstations should be placed in disabled refuge locations as described in Building Regulations Approved Document B and BS9999:2008.
Mounting The Unit
The ViLX-ILB is supplied with a back box. For flush mounting, the cut out is 135mm x 135mm centred on the panel to allow it to be mounted as close to the wall as possible. The surface box is stainless steel with a gland knock-out.
The outstation should be mounted at a height 1200mm from the centre line to the finished floor level to comply with the requirements of Building Regulations Document M (Access for the Disabled) and the measurement requirements of BS5839-9:2011.
Once the outstation is mounted, the supplied sign should be placed adjacent to the outstation to give instructions and identify the point.
Features
- Hands free full duplex operation
- Integral Induction Loop (AFILS)
- Red status LEDs in Call Button
- Green flashing Call Button for location
- Flush or surface mount
- Fully Monitored to BS5839-9:2011
- Braille enhanced Call Button
- Stainless Steel as standard
Specifications
Outstation Cables
- Type : Standard Fire Resistant (Refer to BS5839-9:2011 for exceptions)
- Cores : 2 core 1.5mm screened
- Distance : 500m
Standards Compliance
- EMC :
- EN55103-1
- EN55103-2
- LVD : EN60950
- Product Family :
- BS5839-9
- BS9999
Dimensions & Weight
- Dimensions :
- Flush (HxWxD) : 245x365x7mm
- Surface (HxWxD) : 250x370x45mm
- Cutout (HxWxD) : 135x135x42mm
- Weight :
- Flush : 0.8kg
- Surface : 1.2kg
Downloads
- Datasheet (Adobe PDF)