Shopping Basket

0 Items

Subtotal £0.00

Eaton CF2000 Entry Level Addressable Fire Alarm Panel

£478.55 (inc VAT: £574.26)

Low Stock

SKU: CF2000 Category: Brand:

Summary

The CF2000 fire panel is an entry level addressable control panel that can be configured for either 1 or 2 loop operation. It serves as the optimum solution for buildings that require a simple to use addressable fire system with a single, non-networked panel.

Its ability to support Eaton’s cause and effect programming and a wide range of user-controllable functions make the panel suitable for a varied range of projects from small warehouses to small/medium office developments as well as many small industrial applications.

As with all Eaton addressable panels, the CF2000 uses “spur tolerant” soft addressing to minimise installation time and remove potential for errors often associated with many forms of manual addressing. The fire panel also has an LCD display which provides a simple yet comprehensive, menu-driven, end-user interface.

Small but powerful – an addressable system that packs a punch

  • Ideal for smaller fire system projects, the CF2000 leads to faster installation and ease of panel management as only one panel is required. For larger fire system projects a CF3000 networkable panel may be more suitable.
  • Conventional systems limitations can be overcome using an addressable system: Fire detectors or call points are electronically coded with a unique identification (i.e. ‘address’) that’s programmed to the device during installation, leading to ease of device identification in event of activation.
  • With ’cause and effect’ programming the system can be programmed exactly how you want it, reducing ‘false alarm’ scenarios if, for example, single devices are activated in a particular area.

The easy choice for ‘one panel’ addressable fire systems

CF2000 provides all of the sophisticated features required of a leading edge analogue addressable fire system along with the simple operation and neat installation demanded by installers and building users. The panel can be flush or surface mounted and the generously sized metal back box allows ample facilities for rear or top cable entries. Making it the panel of choice for one panel addressable systems.

Designed with ease of installation at its core

Ease of installation was a guiding principle during the development of the CF2000. Its simple non-networked 1 or 2 loop connectivity, cause and effect programming, pre-drilled mounting holes, ample external cable space and uncomplicated yet comprehensive menu system create a hassle-free experience.

Key Features

  • Simple – Easy to use, single, non-networked panel.
  • User-freindly – Comprehensive, menu-driven, LCD display.
  • Inclusive – Multi-language selection capability.

Specifications

  • Standards : EN54 Pt2 1997, A1:2006 EN54-4 1997, A1: 2002 & A2: 2006
  • Number Of Loops : 2
  • Addresses Per Loop : 200
  • Panel Sounder Circuits : 4 outputs 1A total (programmed in pairs – outputs 1&2, 3&4)
  • Class Change Facility : Operated by external, normally open, volt free contacts
  • Auxiliary Relay : One set of change over contacts, operated in the event of fire activation
  • Auxiliary Fire Routing Equipment Output : Monitored 24Vdc, 30 mA (max)
  • Auxiliary Fire Protection Equipment Output : Monitored 24Vdc, 30 mA (max)
  • Auxiliary Fault Routing Equipment Output : Monitored 12Vdc, 30 mA (max)
  • Output Ports : RS485 and RS232 (for connection of repeaters etc)
  • Mains Input Voltage : 230Vac +10% / -15%
  • System Operating Voltage : 24Vdc
  • Batteries : 2 x 12V 7Ah
  • Standby Duration : 24 hours (dependant on loop loading)
  • Operating Temperature : -5ËšC to 40ËšC
  • Humidity (Non-condensing) : 0 to 93% (+2/-3%) RH
  • Construction :
    • Back Box : Mild Steel
    • Door : PC / ABS
  • Colour : Graphite
  • Dimensions (HxWxD) : 400mm x 320mm x 170mm
  • Weight (with batteries) : 15kg
  • Ingress Protection : IP30
  • Cable Entry :
    • Top : 20 cable entry knockouts (20mm)
    • Bottom : 4 cable entry knockouts
    • Rear : 3 cable entry knockouts & cut-out (125mm x 18mm)

Downloads

Additional information

Weight 15 kg
Max Loops

Protocol

System Type

Touchscreen

Related Products

  • Eaton Cooper USB Analogue Systems Panel Interface

    Eaton Cooper USB Analogue Systems Panel Interface

    • Intelligent addressable control panel to PC site installer connection using the RS232 to USB configuration
    • Wireless control panel to PC site installer connection using the RS232 to USB configuration
    • Wireless control panel to PC wireless live monitor connection using the TTL to USB/RS232 configurations
    • Wireless survey tool to PC survey tool connection using the TTL to USB/RS232 configurations
    • Simple PC driver installation
    • Simple DIP switch configuration

    Low Stock

    £121.41 (inc VAT: £145.69)