    Analogue Programmable Interface

    The analogue control module is designed for use with FyreLine Analogue Linear Heat Detection cables. The control module interfaces between a fire alarm control panel or addressable module and a single zone of Analogue Linear Heat Detection cable.

    The control module monitors the resistance of specially doped polymers within the sensor cable which change as a function of temperature. An abnormal change in resistance along the detection cable triggers either a pre-alarm or alarm on the interface module. The unit is intended to be simple and straightforward to install. Commissioning of the controller can be done using a standard laptop computer or a built-in self-programming module.

    The Analogue control module complies with the latest standards and is housed in an IP66 rated enclosure.

    Approvals

    The FyreLine Analogue Controller is fully approved by the Underwriters Laboratories (UL) and bears the CE mark to show that they comply with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).

    Features

    • UL 521 approved and compliant with the EN54:22 draft standard
    • Self-restorable analogue type system with optional pre-alarm setting
    • Cable based sensing allows detection at the point of risk
    • Low installation, maintenance and repair costs
    • Reliable solution for hazardous areas

    Specifications

      • Dimensions (W x H x D): 182mm x 180mm x 90mm
      • Enclosure Rating : IP66 (IK08) polycarbonate with removable cover
      • Finish: Light grey
      • Operating Temperature Range: 0ºC – 50ºC
      • Supply Voltage: 20 – 28Vdc
      • Humidity: 0% to 90% RH
      • Current Consumption, Normal & Fault: <70mA
      • Current Consumption, Pre-alarm OR Alarm: <80mA
      • Current Consumption, Alarm (& Pre-alarm): <100mA
      • Current Consumption, Fault: <70mA
      • Visual Indicators: ALARM: Red, PRE-ALARM: Red, FAULT: Orange, POWER: Green
      • Relay Outputs: ALARM, PRE-ALARM (all Form C) 2A @ 30Vdc load rating – resistive 0.25A @ 250Vac load rating – resistive
      • Fault Output: Opto-isolated Phototransistor Output Max 50V @ 20mA
      • Remote Reset: Isolated input for resetting module remotely (20-28Vdc pulse for at least 5s)
      • Alarm/Pre-alarm Temperature Range: 54ºC to 100ºC