The Fire Beam Xtra Auto-Aligning Beam Detector With Up To 160m Range

£274.06£321.01

SKU: 4a1c2348043e Category: Brand:

Summary

Soon after we launched the original Fire Beam back in 2005 it became the professional choice in beam detection. Not wanting to rest on our laurels, our world renowned design team has listened to our customers and we have now created the Fire Beam Xtra. Incorporating many of your suggestions and adding our own new innovations, the new Xtra model is a permanent replacement for the original Fire Beam and the outgoing Plus model. The result has further refined this already extraordinary market leader. With new enhanced optics you can cover distances up to 160 metres, meaning for distances over 100 metres you no longer need to use two beams, saving both time and money.

So what’s new with the Xtra model?

New Revised Optics: This new design incorporates all the leading features we have honed over the years and with the latest advanced components we have produced a VdS approved fully compliant to EN 54-12:2015 beam detector that out performs all other beams in the market place.

Five Times Faster: We have designed completely new linear stepper motors which have resulted in amazingly fast commissioning and routine maintenance. Under test conditions at 40 metres we recorded an auto-align time of 3m02s using the Fire Beam straight out of the box. Once aligned a routine re-alignment was timed at just 1m07s. This is class-leading performance not only in terms of speed but also in terms of advanced robust design built for precise purpose.

Multi Language Support: The Fire Beam Xtra has the ability to display seven different languages: English, German, Spanish, French, Italian, Dutch, and Czech. A feature that is welcomed by our ever increasing international customers as we now sell to 62 countries around the world.

Auto-Align On/Off: Although rarely needed, this facility allows you to turn off the auto-alignment in normal service, should the environment be liable to occasional contamination (such as theatres with fake smoke). As motorised beams work by seeing the reflector, if they are unable to because of unavoidable obscuration they can fall out of alignment when trying to find the obscured reflector.The Fire Beam Xtra allows the auto-align feature to be switched off The Fire Beam Xtra will remain in perfect alignment in these environments simply by not trying to re-align itself. Auto-alignment will still continue to work in commissioning modes. This facility is best suited to beams that are mounted on solid surfaces that are not susceptible to building movement at all. For buildings that are liable to movement (such as metal warehouses) we have also built in a new delay function that can be used instead (see below).

Auto-Align Time Delay: Again this facility is useful in environments that are liable to occasional short term obscuration. Adding a delay means that the beam will not check for alignment if the received signal drops for a predetermined time. Pre-set at 4 hours this can be altered to anywhere between 0 to 12 hours if required, to allow the environment to clear.

Beam Phasing: It is possible that beams that face each other will cause problems as their sample rates could coincide and result in unreliable readings, meaning false auto-alignment and unreliably in service. With the introduction of phasing it is now possible to mount beams facing each other with reflectors inbetween. There are up to 7 different sampling rates to choose from, alleviating any cross talk problems.

Hysteresis: Changing the hysteresis will change the delay in returning from a fire state back to a normal state. For example, the beam is factory set at 15% so if the beam falls into fire at 65% (35% threshold) it has to recover 15% to 80% before it returns to normal. This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state. This can be adjusted to anywhere between 1% and 40%. The hysteresis can simply be adjusted from this new menu option.

Features

  • Auto-aligning reflective beam smoke detector.
  • Up to 160m range.
  • Motorised head unit.
  • Controller unit (mounted at low level).
  • Designed to comply with EN54 part 2.
  • Compatible with most major fire panels.
  • Very low power consumption.
  • Uses only 3mA at all times.

Specifications

  • Supply Voltage : 12 to 30 Vdc normal
  • Supply Current : 3.5mA (constant current) in all operational states
  • Constant Current : 17mA (constant current) in fast commissioning
  • Temperature : -10°C to +55°C
  • Humidity : 10 to 95% RH Non-condensing
  • Protection Index : IP65 when suitably mounted and terminated
  • Dimensions:
    • Head : 180mm(H) x 155mm(W) x 137mm(D)
    • Controller : 185mm(H) x 120mm(W) x 62mm(D)
  • Weight : 1.65kg (both parts)
  • Optical Wavelength : 870nm
  • Maximum Angular Alignment : ±5°
  • Maximum Angular Misalignment (static not auto-aligning) : Beam Head ±0.4°, Reflector ±2°
  • Protection Range
    • Standard Product : 7 to 70 metres (use short range mask for distances between 7 & 20 metres)
    • With 70KIT140 Range Kit : 70 to 140 metres
    • With 140KIT160 Range Kit : 140 to 160 metres
  • Alarm Sensitivity Levels : 25%(1.25dB) to 50%(3dB) in 1%(0.05dB) increments (default 35% (1.87dB))
  • Alarm Condition : Obscuration drops to below pre-defined sensitivity level. Time to Alarm Condition adjustable 2 to 30 seconds in 1 second increments (default 10 seconds)
  • Alarm Indication :
    • Controller Status – FIRE
    • Controller Red Flashing LED
    • Head Red Flashing LED
    • Alarm Relay Change Over (CO) Contact
    • Rating 2A @ 30 VDC
  • Test/Reset Features :
    • Beam test function by controller
    • Alarm latching/auto-reset selectable (default auto-reset)
    • Alarm reset in latching mode by controller reset function, removing power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head.
  • Fault Sensitivity Level : 90%
  • Fault Condition :
    • Obscuration drops to below the fault sensitivity level within 1 second, Power Down or Supply Voltage < 9 VDC
    • Commissioning modes, Pre-Alignment and Auto Alignment
    • Beam turned off during Beam Maintenance Time to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds)
  • Fault Indication :
    • Controller Status – FAULT
    • Controller Yellow Flashing LED 1 Second
    • Head Yellow Flashing LED 1 Second
    • Fault Relay Change Over (CO) Contact, Rating 2A @ 30 VDC
  • Normal Condition :
    • Obscuration level is above the Alarm sensitivity level
    • Controller Status – NORMAL
    • Controller Green Flashing LED
    • Programmable on/off
    • Head Green Flashing LED, Programmable on/off
  • Auto-align/Beam Contamination Compensation :
    • Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn’t effect normal operating mode)
    • Beam Contamination Compensation 4 hour monitoring. Compensation data available at the controller

Downloads

Additional information

Weight 5 kg
Version

Standard, Anti-Fog

Anti-Fog

,

Auto-Aligning

Bluetooth Controller

Hazardous Applications

Low Level Controller

Minimum Distance

Range

Type