ClickExpose

Advanced TouchControl Touch Screen Remote Terminal

Advanced

    • (Exc. VAT: )
      • In Stock
    Add To Basket

    Advanced TouchControl Touch Screen Remote Terminal

    TouchControl is a 10", high-resolution touch screen Remote Control Terminal with active maps and zone plans. It is a fire panel and network node in its own right and works on Advanced's standard and fault tolerant networks. It is compatible with our MxPro and Axis EN fire panels. Zone information is presented via both the unit's colour coded, easy-to-navigate interface and the active maps that are easily configured using the Dynamix Tools Map App. Using TouchControl's colour-coded, easy-to-navigate interface users can: Evacuate/Mute/Silence/Resound & Reset View fires/ faults/ disablements/ alarms/ inputs/ outputs/ supervisory and network via ‘instant filters’ View/enable/disable zones View/enable/disable devices Enable/disable outputs by type Enable Walk Test mode Test display/zones/outputs/buzzer and LEDs Quickly access all zones in fire/fault/disablement/test via ‘instant filters’ and where allowed change status View 1,000 general and 500 Fire event log Set network time and date Users can choose from five pre-set background images or upload their own. The relevant zone plan to the unit's position can be displayed and users can run presentations on the display, which defaults to normal operation in the event of a fire condition or if the screen is touched. TouchControl enhances public areas and provides new levels of control and oversight.

    Features

    • 2 Part enclosure for easy first fix and slide-in installation.
    • 1280x800 (720p); high resolution screen, designed to work with fireman's glove
    • 'At a glance' system status, immediately identify zones and devices in Fire, Test, Supervisory and Fault
    • Interactive site maps and zone plans capability built-in
    • Monitored external input for external PSU faults
    • Two-core connection to the network (fault tolerant or standard)
    • Low-profile bezel for flush fitting
    • Select from a number of background images or add a customised image
    • Low profile installation
    • Dedicated status indicators for Fire, Fault, System Fault, Disabled, Test and Power Zone plan display, an essential part of BS5839-1
    • Dual Power Supply inputs, independently monitored to allow redundant power feeds

    Frequently Asked Questions

    How are maps loaded onto the TouchControl repeater?

    The Map Tool software is required which is provided with the product. This software is not licensed or subscription based.

    Specifications

    • Environment : Indoor / Dry
    • Supply Voltage : 10-30VDc
    • Supply Current : 300mA
    • Fuse-PCB : T250H1.6A
    • PSE-Fault Monitoring : EOL 33000 Ohms, Act 680 Ohms
    • Wire Gauge : 2.5mm