Dual Input, Zone Monitor Module with Isolator (EV-ZMU2)
Nittan
Dual Input, Zone Monitor Module with Isolator
EV-ZMU2 is a Loop Powered Dual Input, Zone Monitor module, with integral –ve line Short circuit isolator compatible with Evolution analogue addressable system devices. The Module includes setting options for Class A or Class B Zone input(s). LEDs are provided to Indicate Input active, Fault and Isolator Open. The module is designed to fit the range of standard UK 2-Gang electrical enclosures, including Surface & Flush mount options. Device address may be set using EV-AD2-EXT Hand held programmer. The Short Circuit Isolator will protect the system, whilst allowing the device to continue communication from the opposite side. The isolator will self-reset when the fault clears.
- The Zone Monitor can support the following devices on each Zone Input::
- EVC-P, EVC-H-A2S/CS - 20 units
- EVC-DP (Loop 24V min) - 20 units
- EVC-IR Flame Detector - 5 units
- EVC-PY-IS (Zener Barrier) - 15 units
- The following resistors are required for Fault and Alarm monitoring:
- EOL = 4k7 Ohm
- Alarm = 375 to 680 Ohm - (EVC has Alarm integral to head)
Specifications
- Test Standards: EN54-17: 2005 / AC: 2007 & EN54-18: 2005 / AC: 2007
- CPR Certificate: 0359-CPR-00641
- DoP Number: 00641
- Operating Loop Voltage: 20 to 38 Vdc
- Quiescent current: 10.5 mA (Max)
- Alarm current: 35.0 mA (Max)
- RIL current (If used): 2.5 mA
- Current in short circuit: 15 mA
- Operating voltage (Zone): 12 to 18 Vdc
- Operating temperature: -10°C to +55°C
- Storage temperature: -40°C to +80°C
- Relative humidity : < RH 95% (Non-condensing)
- Cable terminals : 0.75 to 2.5 mm2
- Material : PC/ABS
- Weight: 140g
Downloads
- Datasheet (Adobe PDF)