SigTEL Disable Refuge System 4 or 8 Line Master Controller

C-Tec

    • (Exc. VAT: )
      • In Stock
    Add To Basket

    SigTEL Disable Refuge System 4 or 8 Line Master Controller

    SigTEL comprises a range of low-cost wall-mounting Controllers which can handle 4 or 8 lines (dependent on the model purchased). Typically located in a building’s control room or a fire services access point, each Controller allows management and/or the emergency services to communicate via telephone-style handsets with the system’s ‘outstations’. For larger systems, an 8 line expansion unit allows systems of up to 12 or 16 lines to be easily implemented. An optional network communication card can be used to interlink up to four Master Controllers for systems of up to 64 lines.

    Key Features

    • Allows operators to communicate with the system’s outstations
    • ECU-4 can be connected to up to 4 outstations
    • ECU-8 can be connected to up to 8 outstations
    • Supplied with a backlit LCD and handset
    • Requires 2 x 12V 7.0 Ah batteries
    • Can be semi-flush mounted using the AFP385 bezel
    • Optional tamper-resistant cabinets also available

    Technical Specification

    • Power Suppliy
      • Mains supply : 230 VAC, 50/60 Hz
      • Power supply output : 1 24 VDC
      • Power supply output : 2 5 VDC
      • Output current @ 24 VDC : 0.5 A max
      • Supply and batteries monitored for failure : Yes
      • Standby battery requirements (size and type) : 2 x 12 V, 7 Ah VRLA (Valve Regulated Lead Acid) connected in series
      • Mains fuse 1 A (T) : 20 mm HRC
      • Battery fuse 1 A (F) : 20 mm
      • Max. current draw from battery (Mains failed) : 500 mA (16 Type B outstationsfitted (8 via an ECU-8S), one outstation connected, 15 outstations calling in)
    • Line specification
      • Max. number of lines (ECU-4 version) : 4 (expandable to 12 using ECU-8S expansion unit)
      • Max. number of lines (ECU-8 / ECU-8NT versions) : 8 (expandable to 16 using ECU-8S expansion unit)
      • Number of outstations per line : 1
      • Lines monitored for open and short circuit faults : Yes
      • Outstation cabling requirements : 2 core 1mm2 or 1.5mm2 enhanced fire rated cable, up to 1km perline. Max cable resistance = 40 ohms
    • Output ratings
      • OP1, OP2, OP3 open collector outputs : 24 V, 50 mA max
      • Change-over relay : 30 V, 1 A max
      • 24 V output : 200 mA max
    • Indicators, controls and physical appearance
      • External indicators : LCD display, Disablement, System fault, PSU fault, Generalfault, Power On
      • External controls : Handset (ECU-4 & ECU-8 only), Scroll up, Scroll down, Hold, Call/Accept, Function, Directory, Silence Buzzer
      • Internal controls : Engineer mode button, Reset button
      • Dimensions/ weight : W 412 x H 250 x D 80mm (base); W 435 x H 269 x D 11mm (lid); 3.1kg
      • Physical appearance :  Lid and base RAL7305 (Grey texture), label background Pantone 429C
    • Network specification
      • Max no. of master controllers per network : 4 (any mix of ECU-4s, ECU-8s or ECU-8NTs)
      • Connection : Via ECU721 network communication card, one required per networked master
      • Network cabling requirements : 4 x 2 core 1.5mm2 enhanced fire rated cable, up to 1km in length
    • Optional BF359/3D stainless steel enclosure Dimensions:W 725 x H 448 x D 193mm
    • Optional BF359/2 grey steel enclosure Dimensions:W 603 x H 465 x D 200mm

    Downloads

    Product Reviews

    Review this product

    Same day delivery

    Same Day Dispatch

    Free UK Delivery Over £150*

    Free UK Delivery Over £150*

    Lowest Price Guaranteed

    Lowest Price Guaranteed

    Secure Online Order Processing

    Secure Online Order Processing

    Same Day Dispatch
    Lowest Price Guaranteed
    Free UK Delivery over £150*
    Secure Online Order Processing
    Free Technical Support

    Newsletter Signup

    Enter your details and we'll occasionally send you special offers and product news.