Summary

The EX Pro is a robust & reliable single zone extinguishing panel housed in a modern enclosure. The panel includs a blue 4 x 20 LCD display with a list of extra features such as memory log of fire, fault & system events, adjustable flood times and countdown of extinguishing sequence.

The system is fully comliant with EN54 parts 2 & 4, and EN 12094 part 1.

Idications & Control

Indications

  • Power
  • Fault
  • 1st Stage Alarm
  • 2nd Stage Alarm
  • Gas Fired
  • Bottle Monitoring
  • Manual Release
  • Abort
  • Auto Mode
  • Manual Mode
  • 4 x 20 LCD
  • Common Fire
  • Common Fault
  • General Disablement
  • General Test
  • System Fault
  • Zonal Fire
  • Zonal Fault/Test/Disabled
  • Alarm Active
  • Alarm Fault/Test/Disabled
  • Released
  • Activated
  • Pre-activated
  • Manual Release
  • Flooding Zone Fault
  • Controls Active
  • More Data

Controls

  • Double Action Manual Release
  • Auto/Manual
  • Next
  • Prev
  • Start 1st Stage Sounders
  • Stop 1st Stage Sounders
  • Silence Buzzer
  • Reset
  • Reset CIE
  • LED Test

Features

  • Single extinguishing zone
  • LCD display for simple setup
  • Optional 8-way relay output board
  • Compact repeater available with LED indication & manual release trigger
  • 1.0A bottle output
  • Integrated 2.0 Amp power supply
  • Complies with EN54 parts 2 & 4, and EN 12094 part 1

Specifications

  • General
    • Supply Voltage: 230 AC +/- 10%
    • Battery Space: Up to 2 x 7.0 AH, 12V DC SLA batteries
    • IP Rating: IP32
    • Operating Temperature: -10 to 50°C
    • Box Dimensions (mm): (W) 370 x (H) 311 x (D) 113
  • Detection Zones
    • Zone Capacity: 32 Devices
    • Number of Detection Zones: 2 – EOL (4.7k)
    • Line Monitoring for Open & Short Circuit: Yes
    • Max Cable Length Per Zone: 250m
    • Zone Quiescent Current: 2mA max – EOL
  • Sounder Outputs
    • Number of Sounder Circuits: 3 (S1A, S1B for 1st Stage, S2 for 2nd Stage)
    • Sounder Output Rating: 21-28 VDC, fused at 150mA per circuit
    • Max Cable Length: 60m
  • Auxilliary Outputs
    • Number of Auxilliary Outputs: 5 (fault, 1st stage fire, 2nd stage fire, extract fan, gas fired output)
    • Relay Rating: (30V – 1 Amp)
  • Extinguishant Release Outputs
    • Bottle Output: 1.0 Amp – EOL 18K
    • 5 Monitored Inputs: Manual release, low pressure, gas fired, auto input & abort
    • EOL Value: 18K