Fireray 3000 End to End Infrared Optical Beam Smoke Detector (FFFR3000)
FireRay
FireRay 3000 End to End Infrared Optical Beam Smoke Detector
The FireRay 3000 end to end optical beam smoke detector has been designed to protect large open space applications where standard ceiling mounted smoke detectors would not be suitable. The transmitter head emits an infrared beam to a separate receiver using an LCD display controller. If smoke passes through the beam, the alarm signal is activated. The FireRay 3000 has a programmable sensitivity level, meaning that the alarm activation point can be adjusted to suit environments where dust or exhaust fumes may be present.
Key Features
- Approved to BS EN 54-12:2002
- Ideal for protecting large buildings that use reflective surfaces
- Each kit includes:
- 1 x System Controller - wires into an existing fire alarm control panel
- 1 x Transmitter - projects a narrow beam of infrared light
- 1 x Receiver - receives the beam of infrared light
- An alarm condition is triggered when smoke obscures the beam path
- Configurable operating range of 5m to 120m
- Integrated thumbwheels allow for the infrared beam to be aligned
- Laser alignment aid in the receiver head
- LCD display controller indicates the status of the protected area
- Programmable sensitivity level
- Variable time to fire and time to fault settings
- Automatic Gain Control for signal change caused by dust build up or building movement
- 2 wire installation between controller and receiver
- First Fix concept for ease of installation
- Fire and fault relay contacts on each detector
- 5 year warranty
Technical Specification
- Weight: 0.85kg
- Dimensions (HxWxD): Controller: 124x203x71.5mm, Transmitter & Receiver: 77x78x161mm
- Operating Range : 5 to 120m
- Operating Voltage: 12 to 36V DC +/- 10%
- Operating Current: Controller (with 1 or 2 receivers): 14mA (constant) Transmitter: 8mA (per transmitter)
- IP Rating: IP54
- Relative Humidity (non-condensing): 93%
- Operating Temperature (non-condensing): UL: -20°C to +55°C EN54: -10°C to +55°C
Downloads
- Datasheet (Adobe PDF)