Orbis Intrinsically Safe (IS) Multisensor Detector (ORB-OH-53027)
Apollo
Orbis Intrinsically Safe (IS) Multisensor Detector
The Orbis I.S. Multi-sensor Detector benefits from the same false alarm reduction technology as the optical detector. It is a thermally enhanced smoke detector and so will not give an alarm from heat alone.
Features
- Reduces false alarms.
- Sensitive to fast burning, flaming fires.
- Improved sensitivity to black smoke.
- Compensation for slow changes in sensitivity.
- Algorithms for reliability of alarm.
Specifications
- Sampling Frequency: Once every 4 seconds
- Supply Voltage: 14-28V DC
- Supply Wiring: 2 wires, polarity sensitive
- Polarity Reversal: Not allowed
- Power-up time: < 20 seconds
- Minimum 'Detector Active' Voltage: 12V
- Switch-on Surge Current at 24V: 105uA
- Average Quiescent Current at 24V: 85uA
- Alarm Load: 325 Ohms in series with a 1.0V drop
- Minimum Holding Voltage: 5V
- Minimum Voltage to Light Alarm LED: 6V
- Alarm Reset Voltage: <1V
- Alarm Reset Time: 1 Second
- Remote Output LED (-) Characteristic: 4.7kOhms connected to negative supply
- Material: White Polycarbonate
- Alarm indicator: Integral indicator with 360° visibility
- Dimensions (D x H mm): 100 x 50 mm
- Weight: 80g
- Operating and Storage Temperature: -40°C to +70°C
- Operating temperature is restricted by the intrinsic safety gas
- classification:
- Class T5: -40°C to +40°C
- Class T4: -40°C to +60°C
- The detector must be protected from conditions of condensation or icing
- Humidity: 0% to 98% relative humidity (no condensation)
- Wind Speed: Unaffected by wind
- Atmospheric Pressure: Insensitive to pressure
- IP Rating to EN 6052:1992: 23D
- Electromagnetic Compatibility:
- Emissions: BS EN61000-6-3
- Susceptibility: BS EN50130-4