    Wagner Titanus Micro Sens With Optional RoomIdentification

    The compact and cost-effective air sampling smoke detection system

    Titanus Micro Sens air sampling smoke detec­ tion system was developed as a cost­effective solution for monitoring small to medium­sized spaces and equipment. With the optional ROOM·IDENT, this device makes use of patented technology that enables it to monitor up to 5 rooms or facilities and to identify the source of the fire alarm.

    Titanus Micro Sens is also available in a cold storage option, with a redundant fan, or as a detector box. The detector box option does not have its own fan and can be used in combination with Titanus systems to localise the sampling hole where the smoke is entering. As a fixed system, the Titanus Micro Sens FSA is approved by DIBt.

    A Titanus Micro Sens air sampling smoke detection system can be used to replace up to 8 point­ type smoke detectors. This requires up to 50 m of pipe length, regardless of whether Class A, B or C is required in accordance with EN 54­20.

    Features

    • Early fire detection thanks to innovative, highly sensitive HPLS light source technology.
    • High degree of false alarm immunity through LOGIC·SENS fire pattern recognition.
    • Optional individual room detection of the source of the fire with Room Ident.
    • 1 to 2 alarm thresholds.
    • Optional smoke level display in bar graph form Time saving commissioning through Plug & Play Also available without fan as detector box.
    • Optional with redundant fan Cold storage option available.

    Specifications

    • Max Number Of Sampling Holes : 8
    • Max Pipe Length (With Max Number Of Sampling Holes) : 50m
    • Localisation using Room Ident : Monitoring of up to 5 rooms with localisation of the source of the fire (depending on device configuration)
    • Monitored Area Per Sampling Hole : Corresponds to one point-type smoke detector in accordance with VDE 0833-2
    • Monitoring Of Pipe Systems For Breakage And Obstruction : Optional adjustment for individual hole monitoring (depending on project design)
    • Double-knock Detection : Possible using detector box
    • Sensitivity Detection Unit DM-TM-10 :
      Sampling holes in accordance with EN 54-20: ClassesAmax.2,Bmax.6andCmax.8) 
      • Pre-alarm*: 0.05 % LT/m
      • Main alarm: 0.10 % LT/m
    • Sensitivity detection unit DM-TM-50
      (Sampling holes in accordance with EN 54-20: Class A max. 2, Class B max. 6, Category C max. 8)
      • Pre-alarm*: 0.25 % LT/m
      • Main alarm: 0.50 % LT/m
    • Alarm Notification : 1-2 (Pre and main alarm) (depending on device configuration)
    • Potential Free Contacts, Internal (External, Optional) : 2 (5)
    • Fault Alarms : Cumulative report (Potential free contact, either via NC or NO)
    • Alarm And Fault Relay Power Rating : 1 A, 30 V DC, max. 24 W
    • Clamped Connections : Max. 2.5 mm2
    • Displays On Device
      • Pre-alarm And Main Alarm : 1 red alarm display for each (depending on device configuration)
      • Smoke Level : 10-step bar graph display (depending on device configuration)
      • Fault : Yellow common fault
      • Operation : Green operation display
    • Operating Voltage : 24 V DC (16 - 30 V DC)
    • Max Quiescent Current (at 24 V DC) : 105 mA (at standard fan voltage of 9V)
    • Max Alarm Current (at 24 V DC) : 110-140 mA (at standard fan voltage of 9 V) (depending on device configuration)
    • Starting Current : 150 mA
    • Dimensions (W x H x D) : 140 x 222 x 70 mm3
    • Weight : 850 to 895g (depending on device configuration)
    • Protection Category : Up to IP54
    • Temperature Range : -20°C to + 60°C
      • Cold Storage Option : -40 °C to + 60 °C
    • Humidity (Permanent) : 10 % to 95 % relative humidity
    • Event Log : Built-in
    • Connection Of External Alarm Notifications : Parallel displays and ROOM·IDENT indicators optional
    • Network Capability : Able to accept an Ethernet network card
    • Redundant Fan : Built-in (depending on device configuration)
    • Approved In Accordance With EN 54-20, Classes A, B, C :
      • VdS-No. : G 206004
      • BPRI-No. : 0786-CPD-20322