Hochiki FIRElink-400 4 Pipe Aspirating Smoke Detector

Hochiki

    • (Exc. VAT: )
      • In Stock
    Add To Basket

    Hochiki FIRElink-400 4 Pipe Aspirating Smoke Detector

    Model FIRElink-400 is designed to provide very high sensitivity smoke detection using an aspirating technique. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex set-up.

    The detector is available in three formats, the standard detector (FIRElink-400), the standard detector plus Command Module (FIRElink-400CM) and a standalone Command Module (FIRElink-CM). The Command Module variants provide a single location display, control and interfacing option for systems of up to 127 detectors and allow global programming of all detector functions simultaneously.

     

    Features

    • Volt-free Fire-1 and Fault relay outputs are provided for remote monitoring by local fire detection or BMS systems.
    • High sensitivity provided by laser based forward light scatter for reliable early warning.
    • Four sampling pipes up to 200m (aggregate) in length (still air).
    • False alarms reduced by unique laser sensing technology - able to discriminate against dust.
    • RS485 communications built in as standard for networking and remote communications.

    Specifications

    • Order Code : FIRElink-400 (Standard Detector)
    • Supply Voltage : 21.6 - 26.4 V dc
    • Current Consumption : 470 mA @ 24 V dc at fan speed 8
    • Relay Contact Rating : 500 mA @ 30 V
    • Operating Temperature Range : 0 to +38 °C (UL268), -10 to + 60 °C (CEA4022)
    • Operating Humidity Range : 0 - 90% non-condensing
    • Measurement Range (obs/m) :
      • 0.03% to 25% Full Scale Deflection (FSD)
      • 0.0015% to 25% Sensitivity Resolution
    • Detection Principle : Laser light scattering mass detection and particle evaluation
    • Particle Sensitivity Range : 0.003 μ to 10 μ
    • Dust Discrimination Principle : 3D3 Laser Dust Discrimination (LDD)
    • Maximum Sampling Pipe Length / Diameter : 100m / 3⁄4” nominal bore (27 mm O/D)
    • Total Sampling Pipe Maximum : 200 m @ 100 sampling holes
    • Alarm Levels : 4 (Aux, Pre-alarm, Fire 1 and Fire 2)
    • IP Rating : IP50
    • Sampling Pipe Inlets : 4 on top, 4 at rear
    • Exhaust Air Pipe Outlets : 1 on top, 1 at rear
    • Weight(kg) / Size(mm) : 5.2 / H372 x W427 x D95