Apollo Intelligent Single or Twin Input/Output Unit with Isolator
Apollo
Apollo Intelligent Single or Twin Input/Output Unit with Isolator
The SA4700-102 Intelligent Single Input/Output Unit provides supervision of one or more normally open contacts connected to a single pair of cables and a set of changeover relay output contacts.
The SA4700-104 Intelligent Twin Input/Output Unit provides the function of two Input/Output Units within one enclosure. The two units are electrically independent of each other. There is a DIL switch on each unit to set the address. Both input/output units in the enclosure provide supervision of one or more normally open volt free contacts connected to a single pair of cables and a set of changeover relay output contacts.
Both input/output units in the enclosure provide supervision of one or more normally open volt free contacts connected to a single pair of cables and a set of changeover relay output contacts.
Features
- Singe or Twin input/output interface for Apollo Intelligent Systems.
- Improved design for ease of wiring meaning faster installation.
- Contains controllable isolator.
- Address range 1 - 254.
- Nine pre-configured modes, including compatibility mode from XP95/Discovery to CoreProtocol systems.
- Failsafe mode (meets BS 7273-4 requirements).
- Configurable input styles.
- Earth fault monitoring.
Frequently Asked Questions
When replacing the previous 55000-847 interface, will my system need to be re-programmed?
No installing the SA4700-102 in place of an eixtsing 55000-847 interface is a straight swap with no change in type code. Kindly note to be careful not to set the 8th dip switch, as this is only for when using Core protocol.
Specifications
- Supply Voltage (Vmin-Vmax) : 17-35 V dc
- Protocols : XP95, Discovery and CoreProtocol compatible
- Power-up Surge Current : 900µA
- Quiescent Current : 500 uA
- Max Current LEDs On : 3.5mA
- Max Current LEDs Disabled : 500uA
- Operating Temperature : -40°C to +70°C
- Humidity (No condensation or icing) : 0% to 95% RH
- Vibration, impact & shock : EN 54-17 & EN 54-18
- IP Rating : IP54
- Standards & Approvals : EN 54-17, EN 54-18, CPR, LPCB, VdS, BOSEC, SBSC, FG
- Dimensions : 60mm (H) x 150mm (W) x 90mm (D)
- Weight :
- Single - SA4700-102 : 244g
- Twin - SA4700-104 : 281g
Downloads
- Datasheets
- Single - SA4700-102 (Adobe PDF)
- Twin - SA4700-104 (Adobe PDF)