Shopping Basket

0 Items

Subtotal £0.00

Kentec Sigma CP-A AlarmSense 2, 4 or 8 Zone Panel

£215.13£272.80

SKU: 1f96b26bef07 Categories: , Brand:

Summary

The new Sigma CP-A AlarmSense® range consists of a series of conventional, 2, 4 and 8 zone fire alarm control panels designed and approved in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems – Control and Indicating Equipment.

The AlarmSense® system enables all devices in a given zone to be wired to the same pair of cables thus greatly reducing the cabling and installation requirements and hence costs.

The AlarmSense® range of devices includes smoke and heat detectors, call points, base sounders, base sounder/beacons and relay units – all wired to the same pair of cables.

Having sounders and sounder beacons installed on the same cabling as detectors and call points allows all systems to be configured for common, zonal or two stage alarm by simply setting one of the panels configuration options.

Selection of the AlarmSense® local alarm feature at sounder or sounder beacon bases invokes the alarm verification feature. This is particularly useful in Houses of Multiple Occupation such as student accommodation or nursing homes. When sounder or sounder beacon bases are selected for local alarm mode, any alarm sounders are restricted such that only the sounder connected to the activated detector will operate initially. The panel will attempt to reset the activated detector after a time delay and if successful no further alarms are sounded. If the detector re-activates after being reset, a general alarm will sound throughout the premises. Activation of a second detector or a call point will sound the general alarm immediately.

All control panels have an integral, mains powered battery charger and power supply designed and approved in accordance with the requirements of BS EN54-4.

Features

  • Fully certified to BS EN54-2 and BS EN54-4
  • Available in Surface and Flush Mounting Options
  • Allows systems to be installed in accordance with BS5838: Part 6
  • 2 wire systems, reduces installation cabling
  • 2-wire repeaters and ancillary boards via serial bus
  • Fully programmable using simple menu options
  • Adjustable sounder delay time
  • Sounder configuration options
  • Zonal sounder delay for detectors only
  • Zonal sounder delay for call points only
  • Coincidence output via ancillary board
  • Short circuit fire selectable by zone
  • Non latching selection by zone
  • Silent zones (common sounder outputs)
  • Zone input delay for sprinkler system connection
  • AlarmSense® local alarm feature supported
  • Simple, single board construction
  • Installer friendly
  • Compatible with all AlarmSense® devices
  • Two conventional monitored sounder outputs
  • 3 Amp power supply
  • Auxiliary power output

Specifications

  • Construction : 1.2mm mild sheet steel
  • IP Rating : IP30
  • Finish : Epoxy powder coated
  • Colour – lid & box : BS 00 A 05 grey – fine texture
  • Colour – controls plate & labels : RAL 7047 light grey – satin
  • Weight : 6kg
  • Supply voltage : 230V AC (+10%/-15%)
  • Mains supply fuse : 1.6 Amp 250V
  • Power supply DC rating : 24V 3 Amps
  • Maximum battery size : 7Ah 12V (2 per panel)
  • Fault contact rating : 30V DC 1 Amp
  • Local fire contact rating : 30V DC 1 Amp
  • Fire contact rating : 30V DC 1 Amp
  • Common Sounder output rating : 0.5A per output 
  • AlarmSense Sounder output rating : 0.2A per output
  • Detection zone current : 1.6 milliamps
  • Detection zone EOL resistor : 3K3 5%
  • Sounder output EOL resistor : 10k 5%
  • Cable capacity : 2.5mm² per terminal
  • Operating temperature : -5°C to +40°C
  • Operating humidity : <95% (non condensing)