Shopping Basket

0 Items

Subtotal £0.00

Apollo XP95 High Temperature Heat Detector

£26.58 (inc VAT: £31.90)

In Stock

SKU: 55000-401 Category: Brand:

Summary

The XP95 Heat Detector monitors temperature by using a single thermistor which provides a count output proportional to the external air temperature. The XP95 range features two heat detectors, standard and high temperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C.

Operation:

The XP95 heat detectors have a low air flow resistance case made of self-extinguishing white polycarbonate. The devices monitor heat by using a single thermistor network which provides a voltage output proportional to the external air temperature. The standard heat detectors, 55000-400 and 55000-420, respond to increasing air temperature in such a way that they are classified as an A2S device. Both devices will give 55 counts at 55°C. A high temperature CS heat detector, 55000-401, which can be installed in a typical ambient temperature of 55°C is available. This device will give 55 counts at 90°C.

Application:

The choice of detector from the XP95 range follows the well-established principles of system design. That is, the optimum detector type will depend on the type of fire risk and fire load, and the type of environment in which the detector is sited. For general use, smoke detectors are recommended since these give the highest level of protection. Smoke detectors from the XP95 range may be optical or multisensor types. It is generally accepted that ionisation types have a high sensitivity to flaming fires whereas optical detectors have high sensitivity to smouldering fires.

Features

  • Ideal in environments that are dirty or smoky under natural conditions
  • Well suited for warehouses, loading bays and car-parks
  • Unaffected by wind or atmospheric pressure

Specifications

  • Sensor: Single NTC thermistor
  • Sampling frequency: Continuous
  • Sampling Frequency: 1 second 
  • Sensitivity: 90 OC: 55 counts
  • Supply Wiring: Two wire supply, polarity insensitive
  • Terminal functions: L1 & L2 Loop in & out positive +R Remote indicator positive connection (internal 2.2 kΩ resistance to supply +ve) –R Remote indicator negative connection (internal 2.2 kΩ resistance to supply -ve)
  • Supply voltage: 17 V to 28 V dc
  • Digital communication: XP95, Discovery and CoreProtocol compatible
  • Modulation voltage: 5 V – 9 V peak to peak
  • Quiescent current: 300 µA
  • Power-up surge current: 1mA
  • Duration of power-up surge current: 0.3 seconds
  • Storage temperature: -30°C to +80°C
  • Operating temperature: -20°C to +70°C
  • Humidity (no condensation or icing: 0% to 95% RH)
  • IP Rating: IP54
  • Standards and approvals*:EN54, CPR, LPCB, VdS, BOSEC, SBSC, CCMG, FG
  • Dimensions: 100mm diameter x 42 mm height

Downloads

Additional information

Weight 0.5 kg
Colour

Detection Type

Device Type

Hazardous Applications

Marine Applications

Protocol

System Type

Related Products