GST DC-9102E Conventional Photoelectric Smoke Detector (DC-9102E)
GST
GST DC-9102E Conventional Photoelectric Smoke Detector
The DC-9102E is a photoelectric (optical) detector suitable for use in hotels, restaurants, office buildings, schools, banks, warehouses, libraries, computer rooms, switch rooms, etc.
Application
The detector supports installation on the GST DB-01 conventional detector base for standard applications, or the GST DB-01D diode base when head-out functionality to BS5839 standard is required. Detection sensitivities are programmable using the GST P-9910B device programmer.
Features
- Supports drift compensation to enable good environmental adaptability.
- Self-diagnostic.
- Local test activation with reed switch.
- Chamber contamination checking.
- All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation.
- Configurable polling LED support.
- Remote indicator output.
- Removable sensing chamber for for easy maintenance.
- 2 Programmable smoke sensitivity levels.
Specifications
- Status Indication : Red LED
- User Interface : Via LED - polling,​ fault,​ contamination and alarm
- Compatibility : GST100A Series conventional CIEs as well as GST I-9319 Zone Monitor
- Reset Voltage : <1 VDC
- Reset Time : >2 s
- Alarm Levels : 2
- Connectivity : Zone connection - 2-core (polarity sensitive),​ RI connection - 2-core (polarity sensitive)
- Operating Voltage : 16 VDC to 28 VDC (24 VDC typical)
- Current Consumption :
- <60 μA (Quiescent)
- ≤55 mA (Alarm)
- Detection Principle : Optical
- Sensitivity : Programmable
- Zone Length : Panel dependent
- Remote Alarm Output : 1
- Physical Dimensions : 54.5 mm (including base) x 100 mm Ø
- Net Weight : ±110 g
- Colour : White
- Mounting Type : Ceiling mount
- Material (Body) : ABS
- Cable Specification : >1.0 mm²
- No. Of Cable Cores : 2
- Terminals : 4
- Vandal Proof : No
- Operating Temperature : -10 to +50°C
- Relative Humidity : 0 to 95% noncondensing
- Environment : Indoor
- IP Rating : IP2x
- Environment Temperature :
- -10 to +50°C (Class A1/A2)
- -10 to +65°C (Class B)
- Compliancy : CE,​ WEEE
- Certification : EN54-7
- Standards : LPCB
Downloads
- Installation Sheet (Adobe PDF)