C-Tec XFP Repeater Panel
£268.09 – £368.50
Summary
Can be used to repeat the functions of an XFP Main panel at remote parts of a site (e.g. all potential fire service entrances). Offers all of the functions and controls of an XFP Main panel (access levels 1, 2 and 3). Includes an on-board fault relay. Requires its own dedicated Mains power and battery back-up supply. A maximum of eight XFP Repeaters can be connected to one non-networked XFP Main panel. Communication between the XFP Main panel and Repeater requires a CFP761 network driver card (fitted as standard in all XFP510-16s, available as an optional extra on Main XFP 16 Zone panels). Repeater network wired in 1.5 mm2 two-core screened fire resistant cable. Network length must not exceed 500 metres
Features
- 16 Zone requires – 2 x 12V 3.2Ah VRLA connected in series
- 32 Zone requires – 2 x 12V 7Ah VRLA connected in series
FAQ
How many cables are required to connect a XFP panel to a XFP510-16/XFP510-32 repeater panel?
Just one, two core, fire rated cable.
Specifications
- Protocol/compatibility: Compatible with C-TEC’s XFP CAST, Apollo XP95/Discovery and Hochiki ESP main panels.
- Dimensions (HxWxD): 235 H x 380 W x D 96mm;
- Mains supply : 230V 50/60Hz
- Mains rated current: 350mA maximum
- Internal power supply: 27Vdc nominal
- Total output current limited to: 1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA)
- Auxiliary relays: Fault (Failsafe; Capable of switching 1A @ 30V DC; Must not be used for switching Mains voltages).
- Indicators: 2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault
- Expansion connections: On board CFP761 network driver card facilitates the connection of additional XFP Repeaters.
- Construction & finish: Plastic lid and base; RAL7035 textured
- IP Rating: IP30
- Weight: 1.8kg (without batteries)
- Network specification: Max. no. of Repeaters per Main XFP: 8 (any mix); Max. total length of Repeater network: 500m; Cabling requirements: 1.5mm2 two core screened fire resistant.
- Operating conditions/temperature : -5°C to +40°C. Max relative humidity: 95%
Additional information
Weight | 5 kg |
---|---|
Zones | 16, 32 |