Summary

The Infinity control panel is housed in the most attractive, modern designed, flame retardent ABS enclosurem utilising a switch mode power supply.  It has a fully removable front cover which improves ease of access for cable installations.

Features

  • Access via password – removes problem of lost keys
  • One man test facility
  • Diablement facility for zones & sounders
  • Space for up to 3Ah batteries
  • Sounder delay option
  • 4 Sounder circuits on IN4, 6 & 8.
  • Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies
  • Meets all requirements of latest EN54 part 2 and part 4

Videos

Specifications

  • Mains Voltage : 230V AC +10% / -15% @ 50/60 Hz
  • System Voltage : 24V DC (Nominal)
  • Zone Voltage : 21V DC (Nominal)
  • Sounder Alarm Output :
    • 1-2 Zone : 2 x 150mA @ 24V DC
    • 4-8 Zone:  4 x 150mA @ 24V DC
  • Fault Relay : 1 x Volt Free Relay, SELV @ 1A Max
  • Zone Capacity : 32 Devices Per Zone
  • Remote Sounder Operation : Via N/O Contact Connected to Class Change
  • Sounder Activation Delay : 0 to 9 Minutes in 1 Minuite Increments
  • Zone End of Line : 1N4002 Diode (Cathode Stripe to Zone +ve)
  • Sounder End of Line : 10k Resistor
  • Charger Voltage : 27.6W
  • Battery Cut Off : Battery Voltage Less Than 20V
  • Battery Internal Resistance Limit : 0.9 Ohm
  • Enclosure Size : 375 x 316 x 90 (mm)
  • Weight : 3kg (Excluding Batteries)
  • Maxiumum Battery Space : 2 x 3.4AH, 12Vdc Sealed Lead Acid