    Esento Conventional Remote Display Unit

    LCD remote display fire alarm repeater panel

    LCD remote display unit fire alarm repeater panel, fully functional or passive. Suitable for the Esento conventional panel range (not suitable for Eclipse panels). Can be used on a ESENTO network to display and control across the entire network.

    The Esento, LCD remote display repeater panels have the same, easy to use, controls and indications as the main control panels with the addition of a 4 line x 40 character, backlit LCD display.

    The remote display units are fully functional with ‘Silence’, ‘Resound’ and ‘Reset’ controls, as well as Disable and Test Mode functions. It is also possible to disable the controls for each or all repeater panels to make them passive (indication only). Up to 8 repeater panels can be supported on a network.

    The main circuit board has 2, switch –ve, outputs which provide fire and fault signals. Inputs are available for use as PSU fault inputs. An input for a remote key-switch is also provided.

    A nominal 28v dc supply is required to power the remote display units which can be obtained from the control panel or remote power supply unit.

    Features

    • 4 x 40 character LCD display.
    • Full system control.
    • Fire & fault outputs.
    • Remote key switch input.
    • PSU fault inputs.
    • 28v dc supply input.
    • USB input for PC program upload/download.
    • Test mode, with or without sounders.
    • Disable zones, sounder O/Ps, aux O/Ps & delays.

    Specifications

    • Enclosure : 1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat
    • Cable Entry : Via 20mm knockouts located in the top and rear of the cabinet
    • Dimensions : 305mm W x 204mm H x 42mm D
    • Display : 4 x 40 characted backlit LCD display
    • Input Voltage : Requires 24v dc supply
    • Inputs : Optional key switch input
    • Outputs : 1 x Fire, 1 x Fault 24v dc outputs
    • Communication Wiring
      • Fault tolerant wiring requires 4 core (min 1.5mm) fireproof cable
      • Legacy radial wiring requires 2 core (min 1.5mm) fireproof cable