    Casil LVD Compliant 12V SLA Fire Alarm Battery

    For equipment manufacturers, the IEC 62368-1 standard, under the Low Voltage Directive, is applicable to control & indicating equipment, power supplies and components (if they form an integral part of the equipment), including batteries.

    Batteries fall within IEC62368-1 and the LVD, in relation to their flammability rating and this Casil range meets this requirement.

    Features

    • LVD compliant 12V fire alarm battery.
    • Available from 2.3 to. 38ah sizes.

    Technical Specifications

    • Nominal Voltage : 12V
    • Nominal Capacity
      • CA12-2.2-V2 : 2.2Ah
      • CA12-3.3-V2 : 3.3Ah
      • CA12-7.0-V2 : 7.0Ah
      • CA12-9.0-V2 : 9.0Ah
      • CA12-12-V2 : 12Ah
      • CA12-20-V2 : 20Ah
      • CA12-24-V2 : 24Ah
      • CA12-38-V2 : 38Ah
    • Dimensions (LxWxH)
      • 2.2Ah (CA12-2.2-V2) : 178x34x65mm
      • 3.3Ah (CA12-3.3-V2) : 134x67x65mm
      • 7.0Ah (CA12-7.0-V2) : 151x65x102mm
      • 9.0Ah (CA12-9.0-V2) : 151x65x102mm
      • 12Ah (CA12-12-V2) : 151x99x101mm
      • 20Ah (CA12-20-V2) : 181x76x167mm
      • 24Ah (CA12-24-V2) : 175x166x125mm
      • 38Ah (CA12-38-V2) : 197x165x170mm
    • Weight
      • 2.3Ah (CA12-2.2-V2) : 0.845kg
      • 3.3Ah (CA12-3.3-V2) : 1.22kg
      • 7.0Ah (CA12-7.0-V2) : 2kg
      • 9.0Ah (CA12-9.0-V2) : 2.46kg
      • 12Ah (CA12-12-V2) : 3.3kg
      • 20Ah (CA12-20-V2) : 5.75kg
      • 24Ah (CA12-24-V2) : 7.4kg
      • 38Ah (CA12-38-V2) : 13kg
    • Terminal : F1
    • Container Material : ABS UL94 V2
    • Maximum Discharge Current : 33 A(5S)
    • Internal Resistance (Approximate) :
      • 2.3Ah (CA12-2.2-V2) : 75mΩ
      • 3.3Ah (CA12-3.3-V2) : 65mΩ
      • 7.0Ah (CA12-7.0-V2) : 25mΩ
      • 9.0Ah (CA12-9.0-V2) : 19mΩ
      • 12Ah (CA12-12-V2) : 19mΩ
      • 20Ah (CA12-20-V2) : 15mΩ
      • 24Ah (CA12-24-V2) : 15mΩ
      • 38Ah (CA12-38-V2) : 9.5mΩ
    • Operating Temperature
      • Discharge : -15 to 50°C
      • Charge : 0 to 40°C
      • Storage : -15 to 40°C
    • Nominal Operating Temperatur Range : 25 ± 3°C
    • Cycle Use : 14.4~14.8V (25°C), temperature coefficient -30mV/°C, initial charging current less than 0.69A
    • Standby Use : 13.5V~13.8V (25°C), temperature coefficient -20mV/°C, no limit on initial charging current
    • Capacity Affected By Temperature
      • 40°C : 103%
      • 25°C : 100%
      • 0°C : 86%
    • Self Discharge : Casil CA series batteries may be stored for up to 6 months at 25°C and then a freshening charge is required. For higher temperatures the time interval will be shorter.