This popular conventional fire alarm panel meets the full functional requirements of EN-54 part 2 & 4 and fully certified by the LPCB. The Premier SX is available in 1, 2, 4, 6 and 8 zone versions.
It is housed in a light grey flame retardent ULV0 enclosure, designed to meet modern architectural surrounding, with a removable hinged door. This fire alarm panel has been designed with ease of installation in mind, in addition to the robust electronic design.
Technical Specification
- Detection Zones : 4
- Mains Voltage : 230 VAC +10% / -15% @ 50/60Hz
- System Voltage : 24 VDC (Nominal)
- Zone Voltage : 21 VDC (Nominal)
- Sounder Alarm O/P : 2 x 400 mA @ 24V DC (Nominal)
- Fault Relay Output : 1 x Relay SELV (1 Amp maximum)
- Fire Relay Output : 1 x Relay SELV (1 Amp maximum)
- Zone Capacity : 32 Devices per zone
- Remote Sounder Activation : Via N/O contact (class change)
- Sounder Activation Delay : 0-9 minutes in 1 minute increments
- Zone End of Line : IN4002 Diode (cathode stripe to +)
- Sounder End of Line : 10K Resistor
- Charger Voltage : 28.4V @ 20°C (with battery disconnected)
- Charger Size : 1.1 Amp
- Zone Short Circuit Protection : 100mA
- Charger Short Circuit Protection : Battery Voltage less than 20 V
- Enclosure Size : 355 L x 275 H x 100 D (mm)
- Weight : 3.25kg (Excluding Batteries)
Datasheet & Manuals