The Premier Elite fire alarm panel meets the EN54 part 2 & 4 and is avilable in 5 sizes 1, 2, 4, 6 & 8 zones. It is an economical model of the Premier SX panel nevertheless has all the facilities and functions ideal for small top medium installations.
In addition to the Premier Elite 1 & 2 zone features, the 8 zone versions also have;
- Fault Relay
- Current limited charger to prevent flat batteries drawing too much current
- Built in diode base compatability
- Sounder delay facility
- Connection to optional add on zonal output card
- Zone disablement facility
- One man test facility
The Zone output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel.
Technical Specification
- Supply Voltage : 230V AC +/- 10%
- System Voltage : 24V DC (Nominal)
- Detection Zones : 8
- Zone Voltage : 22V DC
- Zone End of Line : 1N4002 Diode
- Sounder Output : 2 X 400mA @ 24V DC
- Sounder EOL : 10 K Resistor
- Sounder Delay : 0 TO 9 Minutes
- Fire Relay : 1 Relay, SELV @ 1A
- Fault Relay : 1 RELAY, SELV @ 1A (Normally Energised)
- Other Connections
- Class Change Input (N/O Contact)
- Zonal Ooutput Card Interface (20 WY Ribbon)
- Operating Temperature : -0°C to 50°C
- Enclosure Size : 355 X 275 X 100mm
- Weight : 3.25 Kg