New VAT Rate Available - VAT on all products now reduced to 15%
  • Secure on-line ordering
  • Same day dispatch*
  • Sales & enquiries 01792 455 175

Premier Elite 8 Zone Fire Alarm Panel (PE8)

Premier Elite 8 Zone Fire Alarm Panel
  • Premier Elite 8 Zone Fire Alarm Panel
  • Premier Elite 8 Zone Fire Alarm Panel
  • Premier Elite 8 Zone Fire Alarm Panel
  • Price: £172.50 (£150.00 ex VAT)

The Premier Elite fire alarm panel meets the EN54 part 2 & 4 and is avilable in 5 sizes 1, 2, 4, 6 & 8 zones. It is an economical model of the Premier SX panel nevertheless has all the facilities and functions ideal for small top medium installations.

In addition to the Premier Elite 1 & 2 zone features, the 8 zone versions also have;

  • Fault Relay
  • Current limited charger to prevent flat batteries drawing too much current
  • Built in diode base compatability
  • Sounder delay facility
  • Connection to optional add on zonal output card
  • Zone disablement facility
  • One man test facility

The Zone output card gives a drive voltage to operate zonal alarm relays, or a hardwired repeater panel.

Technical Specification

  • Supply Voltage : 230V AC +/- 10%
  • System Voltage : 24V DC (Nominal)
  • Detection Zones : 8
  • Zone Voltage : 22V DC
  • Zone End of Line : 1N4002 Diode
  • Sounder Output : 2 X 400mA @ 24V DC
  • Sounder EOL : 10 K Resistor
  • Sounder Delay : 0 TO 9 Minutes
  • Fire Relay : 1 Relay, SELV @ 1A
  • Fault Relay : 1 RELAY, SELV @ 1A (Normally Energised)
  • Other Connections
    • Class Change Input (N/O Contact)
    • Zonal Ooutput Card Interface (20 WY Ribbon)
  • Operating Temperature : -0°C to 50°C
  • Enclosure Size : 355 X 275 X 100mm
  • Weight : 3.25 Kg

Datasheet & Manual