There are 6 different Fyreye detector bases available for the addressable range of detectors namely, common base, isolator base and addressable relay base.
The Relay base is mainly used where the activation of a particular detector requires a signalto nearby equipment (door holders, or air handling units, for example).
DO NOT CONNECT CONVENTIONAL REMOTE LEDS TO THE -R TERMINAL.
Technical Specification
- Supply Voltage - 17 - 33V DC
- Average Quiescent Current at 24V - 0µA
- Alarm Current At 24V - 15mA
- Isolated Current At 24V - N/A
- Relay Max Switching Power - 30W, 50VA
- Relay Max Switching Current - 1A Res.
- Relay Max Switching Voltage - 50V AC
- Relay Minimum Capability - 10µA, 10mV
- Relay Dropout Voltage - < 6V
- Operating Temperature - -20° to +90° (non condencing or icing)
- Max Wind Speed - Not Affected
- Connections - L1in, L1out (not used), L2, -R (not used), Earth
- Base Size - 100mm diameter x 15mm deep
- Weight - 85.4g