The Fyreye Extra range of analogue detectors have an extra LED to improve detector identifi cation in an alarm condition. The 2 LEDs allow an alarm to be observed from all angles.
The detector works with the Zeta Addressable Protocol, and is compatible with all current Zeta analogue addressable control panels. It comes supplied with a locking grub screw to prevent unauthorised head removal.
The FEAHHE2000 is an analogue addressable fixed heat detector. It will respond with a value of 95 if the detector is triggered through a fixed heat alarm of 90°C.
Technical Specification
- Model : FEAHHE2000
- Detector Class : Fixed Heat Only
- Design Standard : EN54 part 5
- Approval : DIFT
- Operating Voltage : 17 to 28V DC (Plus Protocol)
- Quiescent Current : 440 μA
- Alarm Current : 2.4mA
- Operating Temperature : -10°C to +50°C
- Minimum Continuous Temperature : 0°C
- Maximum Humidity : 95% RH Non Condensing
- Return Value of 55 (Nominal Alarm Level) : Fixed Heat trigger @ 90°C
- Coverage : 50m2
- IP Protection Rating : IP43
- Start-Up Time : 30 seconds
- Size, Diameter x Height (with Base) : 100 x 48 mm (101 x 64 mm)
- Weight (with Base) : 100g (158g)
Datasheet