Premier M Plus 8 Zone Conventional Fire Alarm Panel (PMP8)
Product Options
The Premier M Plus control panels are designed to fulfil the requirements of EN54 parts 2 & 4 as well as being easy to install, operate and maintain.
Being of modular construction, the basic M Plus panel has 8 zone capacity, expandable to 16 and 24 zones.
The Premier M Plus is suitable for surface mounting or semi-flush fitting (with just the door protruding).
Features
- 4 Common sounder circuits (150mA each)
- Optional add-on zonal sounder circuits (50mA Max.)
- Serial repeater output
- Auxiliary supply (29 Volts, 250mA)
- Zone & sounder disablement facility
- Sounder delay facility
- Zonal to common timer (when fitted with zonal sounder boards)
- One man test mode
Technical Specification
- Model: PMP8
- Detection Zones: 8
- Mains Voltage: 230V AC +10% / -15% @ 50/60 Hz
- System Voltage: 24V DC (nominal)
- Zone Voltage: 21V DC
- Sounder Alarm Output: 4 x 150mA @ 24V DC
- Fault Relay Output: 1 x relay SELV @ 1A maximum
- Fire Relay Output: 1 x relay SELV @ 1A maximum
- Zone Capacity: 32 devices
- Remote Sounder Activation: N/A
- Sounder Activation Delay: 0 – 9 minutes in 1 minute increments
- Zone End Of Line: IN4002 Diode
- Sounder End Of Line: 10KΩ Resistor
- Charger Voltage: 28.4V DC (batteries disconnected)
- Zone Short Circuit Protection: 100mA
- Charger Short Circuit Protection: Batteries less than 20V
- Charger Size: 3.0 Amp
- Operating Temperature: 0°C - 50°C
- Enclosure Size: 485 x 477.5 x 125mm
Other Options