The Premier AD 2 loop analogue addressable fire alarm panel has been designed to be as simple to use as a conventional fire alarm panel.
It has 2 addressable loops, divided into 16 zones, and 4 conventional sounder circuits. The sounder circuits operate on common alarm, but can be individually tested or disabled.
The Premier AD supports a serial repeater, and now includes a real time clock, and 2,048 capacity event log. It can also be connected to an RS232 desktop printer for real time event log printing. (Epson LQ300+ recommended)
Technical Specification
- Model : NPAD
- Supply Voltage : 230V AC +/- 10%
- System Voltage : 24V DC (Nominal)
- Number Of Loops : 2
- Loop Capacity : 126 Devices
- Number Of Zones : 16
- Sounder Output : 4 x Conventional Sounder Circuits, 250mA each OR Addressable Sounders
- Fault Output : 1 x Relay Selv @ 1A (Normally Energised)
- Fire Output : 1 x Relay Selv @ 1A
- Operating Temperature : -0°C to 50°C
- Enclosure Size : 485 x 395xX 120mm
- Weight : 6kg
Datasheet