Fike Twinflex Pro 2 Zone Fire Alarm Panel (505 0002)
Product Options
The Fike Twinflex Pro 2 Zone Fire Alarm Panel is an analogue non-addressable panel using a conventional cabling format. Capable of running up to 64 devices in total, devices communicating with the panel do so via the Twinflex data protocol.
This intelligent 2-wire control panel provides 2 circuits (or zones) capable of holding up to 32 devices each. Recognising the difference between manual call points and smoke detectors, the fire alarm system control panel also monitors each fire zone for detector head removal, faults with devices, open or short circuits and end-of-line faults. It also has two monitored outputs that can be configured as sounder circuits.
The attractive panel, with LCD display and keypad for quick configuration, has an integral battery powered power supply unit that can provide up to 72 hours standby time in the event of mains power failure. It also has an event log which can hold up to 500 events, a day/night mode and alarm confirmation mode.
This control panel is only compatible with Twinflex devices and requires one 2-core screened cable for each zone.
Technical Specification
- Dimensions: 331 x 331 x 99 mm
- Operating Temperature: +5C to +40C
- Mains Supply Range: 230V AC, +10%, -15%, 50/60Hz
- Standby Battery Requirement: 2 x 3.3Ah 12v Sealed Lead Acid
- Number Of Zones: 2
- Max Zone Length: 500 Meters
- Zone Loading: 27 SLU (32 Devices Max.)
- Zone Operating Voltage: 29.9V DC Nominal
- Max Zone Current: 250mA
- LCD Display: 4 lines of 20 characters
- Zone Labels: 12 characters
- Event Log: 500 events
- Inputs and Outputs:
- Inputs: 1 x resistance monitored input (3k3 EOL, 680R firing resistor), 2 x un-monitored inputs
- Fault Output: 1 x volt free relay (30V DC @ 1A max.)
- Fire Outputs: 1 x volt free relay (30V DC @ 1A max.), 2 x 24V conventional sounder circuits (10K EOL, 315mA max.)
Approvals
- CE
- BS EN54 2 & 4 (LPCB)
Other Options
Are you interested in this product or know someone that might be?